Application
Solen H1Z2Z2-K Solar cables conforming to European standard ‘EN 50618’ and international standard ‘IEC 62930’ are designed for installations in photovoltaic systems, solar parks, solar farms, rooftop solar systems and in interconnection of solar panels and inverter. They are intended for permanent use outdoor and indoor, for free movable, free hanging and fixed installation. Installation also in conduits and trunkings on, in or under plaster as well as in appliances. Suitable for the application in/at equipment with protective insulation (protection class II).
Conductor: Tinned annealed flexible copper-Class 5 according to IEC 60228
Insulation: Halogen free Cross-linked compound according to EN 50618 Table B.1
Outer Sheath: Halogen free Cross-linked compound according to EN 50618 Table B.1
Sheath Color: Black or Red (Blue and Green-yellow available upon request)
Insulation and sheath are firmly bonded to enhance insulation resistance
Rated Voltage (U o/U)
AC: 1000 / 1000 V
DC: 1500 V
Max Voltage
AC: 1200 / 1200 V
DC: 1800 V
Test Voltage
6,5 kV AC, 15 kV DC (5 min.)
Operating Temperature
-40°C / +90°C Max.
Temperature at Conductor
+120°C based on EN 60216-1 (20.000 h, 50% residual elongation)
Installations Temperature
-25°C / +60°C
Short Circuit Temperature
+250°C Max. 5 sec.
Min. Bending Radius ≥ 4 x D as per EN 50565-1
Cold Bend
EN 60811-504 (-40°C)
Cold Elongation
EN 60811-505 (-40°C)
Cold Impact
EN 60811-506 & EN 50618 (-40°C)
Damp Heat Test
EN 50618 (1000h, 90°C & 85% humidity)
Halogen Free Properties
EN 50525-1 (Annex B)
Low Smoke Emission EN 61034-2 (Light transmittance > 60%) Flame Retardancy EN 60332-1-2
Weather Resistance EN 50618 (Annex E)
Acid and Alkaline Resistance EN 50618 (Annex B)
Shrinkage Test EN 50618, (Table 2)
Durability of Print EN 50618
Long Term Resistance of Insulation to DC
EN 50395 Clause 9 IEC 62821-2
| PART NO. | NUMBER OF CORES | CROSS SECTIONS mm2 |
CONDUCTOR DIAMETER (mm.) |
OVERALL DIAMETER |
BENDING RADIUS |
WEIGHT kg/km |
| SPV50015CL000 | 1 | 1,5 | 1,6 | 4,50-0,2 /+0,3 | 22 | 31 |
| SPV50025CL000 | 1 | 2,5 | 2 | 4,90-0,2 /+0,3 | 24 | 40 |
| SPV50040CL000 | 1 | 4 | 2,5 | 5,50-0,2 /+0,3 | 26 | 56 |
| SPV50060CL000 | 1 | 6 | 3 | 5,90-0,2 /+0,3 | 30 | 73 |
| SPV50100CL000 | 1 | 10 | 4 | 6,90-0,2 /+0,3 | 35 | 115 |
| SPV50160CL000 | 1 | 16 | 5 | 8,30-0,2 /+0,5 | 42 | 176 |
| SPV50250CL000 | 1 | 25 | 6,1 | 10,00-0,3 /+0,5 | 50 | 261 |
| SPV50350CL000 | 1 | 35 | 7,4 | 11,40-0,3 /+0,5 | 57 | 368 |
| SPV50500CL000 | 1 | 50 | 8,8 | 13,20-0,3 /+0,5 | 65 | 513 |
| SPV50700CL000 | 1 | 70 | 10,5 | 15,10-0,3 /+0,8 | 76 | 700 |
| SPV50950CL000 | 1 | 95 | 11,9 | 16,90-0,3 /+0,8 | 85 | 912 |
| SPV50120CL000 | 1 | 120 | 13,4 | 19,20-0,5 /+0,8 | 115 | 1153 |
| SPV50150CL000 | 1 | 150 | 14,8 | 21,70-0,3 /+0,8 | 130 | 1425 |
| SPV50185CL000 | 1 | 185 | 16,5 | 23,90-0,5 /+0,8 | 143 | 1776 |
| SPV50240CL000 | 1 | 240 | 18,9 | 27,00-0,5 /+0,8 | 162 | 2303 |
TÜV NORD approval certified
UKCA-CPR rating Dca to BS EN 50575 (1x4 – 1x6 – 1x10mm2)
Expected service lifetime (Min. 25 years acc. to EN 50618)
Higher insulation resistance
High current carrying capacity
Compatible for all major connectors
AD8 water submersion compatible
AG2 Medium severity impact resistance
Ammonia Resistance
Salt Water Resistance
Suitable for wet, damp and humid locations
Excellent flexibility
Good stripping performance from conductor
Abrasion resistant
UV, Oil, Grease and Ozone resistant
Acid and Alkaline resistant
Anti rodent and Anti termite versions are available.
Direct Burial
Do not Contain Fish Oil
DIRECT BURIAL CONDITIONS:
Allowed to be direct burial to earth that does not contain any damaging chemicals, solvents, rodents, termites etc.
Proper and correct installation methods based on VDE 0800-174 and VDE 0891-6 should be applied.
Necessary cautions should be taken to avoid physical damage of cables during installation.
It is better that installation to be in pipes/conduits/concrete channels.