SOLEN CLASSIC H1Z2Z2-K

 

Application

Solen H1Z2Z2-K Solar cables conforming to European standard ‘EN 50618’ and international standard ‘IEC 62930’ are designed for installations in photovoltaic systems, solar parks, solar farms, rooftop solar systems and in interconnection of solar panels and inverter. They are intended for permanent use outdoor and indoor, for free movable, free hanging and fixed installation. Installation also in conduits and trunkings on, in or under plaster as well as in appliances. Suitable for the application in/at equipment with protective insulation (protection class II).


Data Sheet

Conductor:  Tinned annealed flexible copper-Class 5 according to IEC 60228

Insulation:  Halogen free Cross-linked compound according to EN 50618 Table B.1

Outer Sheath:  Halogen free Cross-linked compound according to EN 50618 Table B.1

Sheath Color:  Black or Red (Blue and Green-yellow available upon request)

Insulation and sheath are firmly bonded to enhance insulation resistance

Rated Voltage (U o/U)
AC: 1000 / 1000 V
DC: 1500 V

Max Voltage
AC: 1200 / 1200 V 
DC: 1800 V

Test Voltage 
6,5 kV AC, 15 kV DC (5 min.)

Operating Temperature  
-40°C / +90°C Max.

Temperature at Conductor
+120°C based on EN 60216-1  (20.000 h, 50% residual elongation)

Installations Temperature
-25°C / +60°C

Short Circuit Temperature
+250°C Max. 5 sec.

Min. Bending Radius ≥ 4 x D as per EN 50565-1

Cold Bend
EN 60811-504 (-40°C)

Cold Elongation
EN 60811-505 (-40°C)

Cold Impact
EN 60811-506 & EN 50618 (-40°C)

Damp Heat Test
EN 50618 (1000h, 90°C & 85% humidity)

Halogen Free Properties
EN 50525-1 (Annex B)

Low Smoke Emission EN 61034-2 (Light transmittance > 60%) Flame Retardancy EN 60332-1-2

Weather Resistance EN 50618 (Annex E)

Acid and Alkaline Resistance EN 50618 (Annex B)

Shrinkage Test EN 50618, (Table 2)

Durability of Print EN 50618

Long Term Resistance of Insulation to DC
EN 50395 Clause 9 IEC 62821-2

 

PART NO. NUMBER OF CORES CROSS SECTIONS
mm2
CONDUCTOR
DIAMETER
(mm.)
OVERALL
DIAMETER
BENDING 
RADIUS
WEIGHT
kg/km
SPV50015CL000 1 1,5 1,6 4,50-0,2 /+0,3 22 31
SPV50025CL000 1 2,5 2 4,90-0,2 /+0,3 24 40
SPV50040CL000 1 4 2,5 5,50-0,2 /+0,3 26 56
SPV50060CL000 1 6 3 5,90-0,2 /+0,3 30 73
SPV50100CL000 1 10 4 6,90-0,2 /+0,3 35 115
SPV50160CL000 1 16 5 8,30-0,2 /+0,5 42 176
SPV50250CL000 1 25 6,1 10,00-0,3 /+0,5 50 261
SPV50350CL000 1 35 7,4 11,40-0,3 /+0,5 57 368
SPV50500CL000 1 50 8,8 13,20-0,3 /+0,5 65 513
SPV50700CL000 1 70 10,5 15,10-0,3 /+0,8 76 700
SPV50950CL000 1 95 11,9 16,90-0,3 /+0,8 85 912
SPV50120CL000 1 120 13,4 19,20-0,5 /+0,8 115 1153
SPV50150CL000 1 150 14,8 21,70-0,3 /+0,8 130 1425
SPV50185CL000 1 185 16,5 23,90-0,5 /+0,8 143 1776
SPV50240CL000 1 240 18,9 27,00-0,5 /+0,8 162 2303

TÜV NORD approval certified
UKCA-CPR rating Dca to BS EN 50575 (1x4 – 1x6 – 1x10mm2)
Expected service lifetime (Min. 25 years acc. to EN 50618) 
Higher insulation resistance
High current carrying capacity
Compatible for all major connectors
AD8 water submersion compatible 
AG2 Medium severity impact resistance
Ammonia Resistance
Salt Water Resistance
Suitable for wet, damp and humid locations
Excellent flexibility
Good stripping performance from conductor
Abrasion resistant
UV, Oil, Grease and Ozone resistant
Acid and Alkaline resistant
Anti rodent and Anti termite versions are available.
Direct Burial
Do not Contain Fish Oil


DIRECT BURIAL CONDITIONS:
Allowed to be direct burial to earth that does not contain any damaging chemicals, solvents, rodents, termites etc.
Proper and correct installation methods based on VDE 0800-174 and VDE 0891-6 should be applied.
Necessary cautions should be taken to avoid physical damage of cables during installation.
It is better that installation to be in pipes/conduits/concrete channels.