Conductor: Tinned annealed flexible copper-Class 5 according to EN 60228
Insulation: Halogen free Cross-linked compound, “Type EI 5” according to EN 50363-5
Colour: Green/Yellow, Black and all other colors are available upon request
Rated Voltage (U0/U)
AC 450 / 750 V
Test Voltage
AC 2,5 kV
Operating Temperature
-40°C / +90°C
Insulation Temperature
-5°C / +60°C
Short Circuit Temperature
+250°C (Max. 5 sec.)
Min. Bending Radius
(As per EN50525-1 Table.3)
4 x D for cable D ≤ 8 mm
5 x D for cable 8 mm < D ≤ 12 mm
6 x D for cable D > 12 mm
Electrical Test
EN 50395
Non-electrical Tests
EN 50396
Insulation Resistance
EN 50525-3-41 Table B.2
Ozone Resistance
IEC 60811-403, EN 50396 Clause 8.1.2
UV Resistance
IEC 62930:2017 (Annex E), EN 50618 (Annex E)
Halogen Free Properties
EN 50525-1 (Annex B), IEC 60764-1, EN 50363-5
Low Smoke Emission
EN 61034-1 / 2 (Light transmittance > 80%)
Flame Retardancy
EN 60332-1-2
| CABLE TYPE | CROSS SECTIONS |
OVERALL DIAMETER |
BENDING RADIUS |
CABLE WEIGHT approx. |
|||
| n x mm2 | mm | (min.) mm | kg/km | ||||
| H07Z-K | 1 | G | 1,5 | 2,9 | -0,6 | 11,6 | 19 |
| H07Z-K | 1 | G | 2,5 | 3,5 | -0,6 | 14 | 29 |
| H07Z-K | 1 | G | 4 | 4,1 | -0,6 | 16,4 | 43 |
| H07Z-K | 1 | G | 6 | 4,5 | -0,6 | 18 | 59 |
| H07Z-K | 1 | G | 10 | 5,9 | -0,6 | 23,6 | 103 |
| H07Z-K | 1 | G | 16 | 6,9 | -0,6 | 27,6 | 157 |
| H07Z-K | 1 | G | 25 | 8,5 | -0,6 | 42,5 | 239 |
| H07Z-K | 1 | G | 35 | 9,8 | -0,6 | 49 | 347 |
| H07Z-K | 1 | G | 50 | 11,6 | -0,6 | 58 | 479 |
| H07Z-K | 1 | G | 70 | 13,3 | -1 | 79,8 | 654 |
| H07Z-K | 1 | G | 95 | 15,3 | -0,625 | 91,8 | 866 |
| H07Z-K | 1 | G | 120 | 17,4 | -0,625 | 104,4 | 1.095 |
| H07Z-K | 1 | G | 150 | 19,3 | -0,625 | 115,8 | 1.338 |
| H07Z-K | 1 | G | 185 | 21,5 | -0,625 | 129 | 1.678 |
| H07Z-K | 1 | G | 240 | 24,6 | -0,625 | 147,6 | 2.194 |
REACH and RoHS Complaint
CE conformity
UV & Ozone Resistant
General requirements acc. to EN 50525-1
Guide to use acc. to EN 50565-1
CPR rating Dca acc. to EN 50575