H1Z2Z2-K

 

Application

Solen H1Z2Z2-K Solar cables conforming to European standard ‘EN 50618’ and international standard ‘IEC 62930’ are designed for installations in photovoltaic systems, solar parks, solar farms, rooftop solar systems and in interconnection of solar panels and inverter. Suitable for fixed installations within pipes or systems, indoor or outdoor solar applications, installations where fire, smoke emissions and toxic fumes pose potential risks to life and equipment.


Data Sheet

Conductor:  Tinned annealed flexible copper-Class 5 according to IEC 60228

Insulation:  Halogen free Cross-linked compound according to EN 50618 Table B.1

Outer Sheath:  Halogen free Cross-linked compound according to EN 50618 Table B.1

Sheath Color:  Black or Red (Blue and Green-yellow available upon request)

Rated Voltage (U o/U)
AC: 1000 / 1000 V
DC: 1500 V

Max Voltage
AC: 1200 / 1200 V 
DC: 1800 V

Test Voltage 
6,5 kV AC, 15 kV DC (5 min.)

Operating Temperature  
-40°C / +90°C Max.

Temperature at Conductor
+120°C based on EN 60216-1  (20.000 h, 50% residual elongation)

Installations Temperature
-25°C / +60°C

Short Circuit Temperature
+250°C Max. 5 sec.

Min. Bending Radius ≥ 4 x D as per EN 50565-1

Cold Bend
EN 60811-504 (-40°C)

Cold Elongation
EN 60811-505 (-40°C)

Cold Impact
EN 60811-506 & EN 50618 (-40°C)

Damp Heat Test
EN 50618 (1000h, 90°C & 85% humidity)

Halogen Free Properties
EN 50525-1 (Annex B)

Low Smoke Emission EN 61034-2 (Light transmittance > 60%) Flame Retardancy EN 60332-1-2

Weather Resistance EN 50618 (Annex E)

Acid and Alkaline Resistance EN 50618 (Annex B)

Shrinkage Test EN 50618, (Table 2)

Durability of Print EN 50618

Long Term Resistance of Insulation to DC
EN 50395 Clause 9 IEC 62821-2

 

PART NO NUMBER
OF CORES
CROSS-
SECTIONS
(mm2)
NOMINAL
OVERALL
DIAMATER
(mm.)
BENDING
RADIUS
(min) (mm.)
WEIGHT
(kg/km)
CONDUCTOR
RESISTANCE
(at 20 oC Ω/km)

CURRENT CARRYING CAPACITY
At max. 120°C conductor temp.

(A) 

SHORT CIRCUIT
CURRENT
              Single Cable
in Free Air

Single Cable
on Surface
Two Loaded
Cables Touching
On a Surface
(5s. from 90 oC to 250 oC)
kA
SPV50015CL000 1 1,5 4,5  
-0,2 /+0,3
22 33 13,7 30 29 24 0,09
SPV50025CL000 1 2,5 4,90
-0,2 /+0,3
24 41 8,21 41 39 33 0,15
SPV50040CL000 1 4 5,5
-0,2 /+0,3
26 57 5,09 55 52 44 0,25
SPV50060CL000 1 6 5,90
-0,2 /+0,3
30 73 3,39 70 67 57 0,37
SPV50100CL000 1 10 6,90
-0,2 /+0,3
35 110 1,95 98 93 79 0,63
SPV50160CL000 1 16 8,00
-0,2 /+0,3
40 170 1,24 132 125 107 1
SPV50250CL000 1 25 10,00
-0,2 /+0,3
50 260 0,795 176 167 142 1,6
SPV50350CL000 1 35 11,00
-0,2 /+0,3
56 360 0,565 218 207 176 2,2
SPV50500CL000 1 50 13,20
-0,2 /+0,3
65 500 0,393 276 262 221 3,2
SPV50700CL000 1 70 14,90
-0,3 /+0,5
75 715 0,277 347 330 278 4,40
SPV50950CL000 1 95 16,70
-0,3 /+0,5
83 933 0,21 416 395 333 6,00

TÜV NORD approval certified
REACH and RoHS Complaint
CPR rating Dca acc. to EN 5057 5 (Cca upon request)
Expected lifetime (Min. 25 years acc. to EN 50618)
Higher insulation resistance
High current carrying capacity
Compatible for all major connectors
AD8 water submersion compatible
(internal tested – referred to test method EN 50525-2-21 Appendix E)
Suitable for and wet, damp and humid locations
Excellent flexibility
Good stripping performance from conductor
Abrasion resistant
UV, Oil, Grease and Ozone resistant
Resistance against Ammonia
Acid and Alkaline resistant
Anti rodent and Anti termite versions are available.

DIRECT BURIAL CONDITIONS:
Allowed to be direct burial to earth that does not contain any damaging chemicals, solvents, rodents, termites etc.  Correct installation methods based on VDE 0800-174 and VDE 0891-6 have to be applied and necessary cautions should be taken to avoid physical damage of cables during installation. Burial in pipes/conduits/channels will give you better and safer installation.