  Application

Solen H07Z-K is a flexible cable for fixed installation to usage as earthing wire and for wiring of lamps, appliances, switchgear cabinets, panels and distribution boxes, especially when a low fume and corrosive gas emission (such as hotels, public and government buildings) is required.


Data Sheet

Conductor: Tinned annealed flexible copper-Class 5 according to EN 60228
Insulation: Halogen free Cross-linked compound, “Type EI 5” according to EN 50363-5
Colour: Green/Yellow, Black and all other colors are available upon request

Rated Voltage (U0/U)
AC  450 / 750 V
Test Voltage
AC  2,5 kV
Operating Temperature
-40°C / +90°C
Insulation Temperature
-5°C / +60°C
Short Circuit Temperature
+250°C (Max. 5 sec.)
Min. Bending Radius
(As per EN50525-1 Table.3)
4 x D  for cable   D  ≤ 8 mm
5 x D    for  cable       8 mm <  D ≤ 12 mm 
6 x D    for cable        D > 12 mm
Electrical Test
EN 50395
Non-electrical Tests
EN 50396
Insulation Resistance
EN 50525-3-41 Table B.2
Ozone Resistance
IEC 60811-403, EN 50396 Clause 8.1.2 
UV Resistance
IEC 62930:2017 (Annex E), EN 50618 (Annex E)
Halogen Free Properties
EN 50525-1 (Annex B), IEC 60764-1, EN 50363-5
Low Smoke Emission
EN 61034-1 / 2 (Light transmittance > 80%)
Flame Retardancy
EN 60332-1-2

 



NUMBER OF CORES

CROSS
SECTIONS

mm2

OVERALL
DIAMETER
mm

BENDING RADIUS
(min.) mm

WEIGHT

kg/km

CONDUCTOR
RESISTANCE
20 oC
ohm/km

CURRENT CARRYING
CAPACITY
(*) A

SHORT CIRCUIT
CURRENT

 

 

   

 

 

 

(5s.From 90oC to 250oC) kA

1 6 4,50  -0,2 /+0,3 19 61 3,39 54 0,37

REACH and RoHS Complaint
CE-CPR rating Dca,s2,d2,a1 acc. to EN 50575
UV & Ozone Resistant
General requirements acc. to EN 50525-1
Guide to use acc. to EN 50565-1